Analysis of Capacitor Unbalance Protection activation due to AC filter tripping incident at ±660kV HVDC Lahore converter station

Are you an author of this work?Link to your sovereign AfriScholar profile
Published in: Journal of Engineering Research and Reviews
Publisher: Eldaghayes Publisher • Libya • 3041-4822
DOI: https://doi.org/10.5455/jerr.20250102040226

Abstract

This study examines an AC filter tripping incident that occurred at Lahore Converter station of ±660kV high voltage direct current (HVDC) Pak Matiari-Lahore transmission project which seriously affected the stable operation of the converter station. The fault current exceeded the trip threshold and lasted for more than 20 milliseconds, causing the activation of capacitor unbalance protection. The short circuit discharge phenomenon occurring between the layers of the capacitors is responsible for tripping the filter leading to the activation of capacitor unbalance protection. The incident emphasizes how important protection methods are to maintaining system stability in unusual circumstances. The fault mechanism is thoroughly examined, including its underlying causes and modes of transmission. In order to prevent the expensive equipment from damage, the study highlights the importance of precise protective settings. To reduce future dangers, suggestions are made for better operation and maintenance procedures and cutting-edge monitoring systems. By taking these measures, the AC filter's robustness and dependability will be improved, especially during difficult grid circumstances like periods of high demand.

Download Full Text PDFCrossref RecordCrossref XML

Verified Citation Velocity

Recorded scholarly citations in African and international peer-reviewed literature

0
Total Citations

Citations are continuously tracked and harvested across continental OJS endpoints and OpenAlex feeds.